Cummins diesel generator set,for Landuse
Engine of CUMMINS E45GL Diesel Generator Set for Landuse |
Engine model | DCEC Cummins 4BTA3.9-G2 |
No. of cylinders | 4(in-line) |
Displacement (L) | 3.9 |
Induction system | Exhaust turbocharged, water-air inter-cooling |
Combustion system | AD type fuel pump |
Bore*Stroke(mm) | 102*120 |
Compression ratio | 16.5:1 |
Rated speed(rpm) | 1500 |
Maximum power(KW/HP) | 65/88.4 |
speed control system | High precision elelectrical speed governor |
exhaust smoke level(m3/min) | 14.8 |
Exhaust temperature(°C) | 497 |
Maxium exhaust back pressure(kPa) | 10 |
Maxium intake pressure(kPa) | 6.2 |
Air consumption(m3/min) | 5.9 |
Air flow(m3/min) | 158 |
100% load fuel consumption(L/H) | 13 |
The total capacity of oil(L) | 10.9 |
Oil consumption(g/kwh) | ≤4 |
Oil sump capacity(L) | 14.3 |
Rated oil pressure(kPa) | 350 |
Coolant capacity (engine and radiator)(L) | 14.3 |
Thermostat opening temperature(°C) | 83-95 |
Maximum water temperature(°C) | 100 |
| |
Alternator of CUMMINS E45GL Diesel Generator Set for Landuse |
Alternator model(Stamford) | UCI224E |
Alternator model(Marathon) | MP-48-4 |
Alternator model(Engga) | EG225S-50N |
Phase | 3 |
Winding connection | 4 wire 3 phase ,Y type |
Starter battery capacity(Ah) | 90*2 |
Starter battery voltage(V) | 24 |
No. of bearings | 1 |
Power factor | 0.8 |
Protection class | IP23 |
Altitude requirement(m) | ≤1000 |
Excitation mothod | Brushless |
Insulation class /temperature class | H/H |
Steady- state voltage reguation | ≤±1% |
Alternator capacity | 60KVA |
Alternator efficiency | 88.80% |
Cooling air flow(m3-s) | 0.216 |
voltage regulate range | ≥±5% |
Steady-state voltage reguation | ≤±1% |
Transient voltage deviation(100% sudden power reduction) | ≤+25% |
Transient voltage deviation(sudden power incremen) | ≤-20% |
Voltage stabilization time (100% sudden power reduction)(S) | ≤6 |
Voltage stabilization time (sudden power increment) (S) | ≤6 |
Steady-state frequency regulation | 0-5% adjustable |
Frequency volatility | ≤0.8% |
Transient frequency deviation (100% sudden power reduction) | ≤+12% |
Transient frequency deviation (sudden power increment) | ≤-10% |
Frequency recovery time(100% sudden power reduction)(S) | ≤5 |
Frequency recovery time (sudden power increment)(S) | ≤5 |
| |
1) Deutz 413,513 series engine, Deutz 912.913 series engine, Deutz 1012,1013,1015 ,2012 series
2) Deutz D302 series ,TBD226 series,TBD 234 series, TBD 600 series, TBG 600 series
3) MTU 396TB series, 396SE Series 396TC/TB/TE series ,956 series
4) IVECO Cursor 9,NEF6, F1C engine
5) VM R425 DOHC,VM R428 DOHC,VM D704/D754 Series motor
6) Cummins M11,NT/NTA-855, KT/KTA/KTTA19,KT/KTA38, KTA/KTTA50, 4BT,6BT, C serials engine
7) Diesel engine spare parts
8) QD32T/TI engine
9) 4JA1,4BD1,6BD1
10) Lovol 1004 series and 1006 series
11) Pielstick PC2.2, 2.3, 2.4, 2.5, 2.6 PA6L-280,
12) Doosan P086TI and P086TI-1
13) GM6.5 engine
14) Cummins diesel generator set